Schneider Electric

ABLS1A24100

ABLS1A24100 Schneider Electric

The product image shown is for illustration purposes only and may not be an exact representation of the product. Please refer to the item description for accurate information

Please note: Some products are subject to manufacturer minimum pack quantities. We will confirm this at time of order.

Description for ABLS1A24100 Schneider Electric

ABLS1A24100 Schneider Electric - Regulated Power Supply, 100-240V AC, 24V 10 A, single phase, Optimized

Extended Description for ABLS1A24100 Schneider Electric

ABLS1A24100 Schneider Electric - This ABLS regulated switch mode power supply (SMPS) supplies direct current voltage.,It has a rated input of 100V to 240V AC and 140 V to 340 V DC, a rated output current of 10A at 24V DC and a rated power output of 240W.,It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water.,It installs on omega rail or fixing by screw. Its width is 60mm, its height is 123,6mm, its depth is 117,6mm.,It ensures a protection against overloads and short-circuits with automatic restart after the source of overload/short-circuit has been corrected.,It weighs 0.800kg.,It is a power supply for industrial use, rail mounting.,It conforms to EN62368-1, ENIEC61010-1/2-201, ENIEC61204-3, EN61000-6-1/2/3/4, EN61000-3-2-3, UL62368-1, UL61010-2-201/-1-201, CSAC22.2No62368-1/No61010-2-201/No61010-1 standards, and certified by CE, CUL listed/recognized, RCM, CBscheme.,The Acti9 iC60 range of Miniature Circuit Breakers is recommanded for its protection. The type of protection is 6A, B or C curve.,It has in the front face a LED indicating presence of DC output voltage, and a QR code for access to the latest technical documentation.,Thanks to its book housing, it can be installed either in enclosures or industrial panels by clipping on omega (DIN) rail.,It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness.

Free Delivery to UK Mainland on orders over £25

Manufacturer New

5 available
1 - 2 w.days
£222.87 Exc. VAT
£267.44 Inc. VAT

Manufacturer New

5 available
5 - 8 w.days
£296.72 Exc. VAT
£356.06 Inc. VAT

Direct from Manufacturer

Available on back order
4 - 6 W.Weeks
£96.88 Exc. VAT
£116.26 Inc. VAT

Main

range of product Modicon Power Supply
product or component type Power supply
power supply type Regulated switch mode
Variant option Optimized
Enclosure material Aluminium
Nominal input voltage 100...240 V AC single phase,100...240 V AC phase to phase,140...340 V DC
Rated power in W 240 W
Output voltage 24 V DC
Power supply output current 10 A

Complementary

Input voltage limits 85...264 V AC without temperature derating,120...375 V DC without temperature derating
Nominal network frequency 50…60 Hz
Network system compatibility TN,TT,IT
Maximum leakage current 1 mA 240 V AC
Input protection type Integrated fuse (not interchangeable) 6.3 A,External protection (recommended) 20 A Curve B,External protection (recommended) 20 A Curve C,External protection (recommended) 6 A Curve B,External protection (recommended) 6 A Curve C
Inrush current 30.0 A at 115 V,60.0 A at 230 V
Power factor 0.95 at 115 V AC,0.95 at 230 V AC
Efficiency 85 % at 115 V AC,88 % at 230 V AC
Output voltage adjustment 22...28 V
Power dissipation in W 36 W
Current consumption < 2.8 A 115 V AC,< 1.4 A 230 V AC,< 2.4 A 140 V DC
Turn-on time < 1 s
Holding time > 20 ms 115 V AC,> 20 ms 230 V AC
Startup with capacitive loads 8000 µF
Residual ripple < 120 mV
Meantime between failure [MTBF] 700000 h at 25 °C, full load conforming to SR 332
Output protection type Against overload and short-circuits, protection technology: automatic reset,Against over temperature, protection technology: manual reset,Against overvoltage, protection technology: manual reset
Connections - terminals Screw connection: 0.5...4 mm², (AWG 20...AWG 12) without wire end ferrule for output,Screw connection: 0.5...2.5 mm², (AWG 20...AWG 14) with wire end ferrule for output,Screw connection: 0.75...4 mm², (AWG 18...AWG 12) without wire end ferrule for input,Screw connection: 0.75...4 mm², (AWG 18...AWG 12) with wire end ferrule for input
Line and load regulation < 0.5 % at 0 to 100 % load at 25 °C,< 1 % at full voltage range in line at 25 °C
Status LED 1 LED (green) output voltage
Depth 117.6 mm
Height 123.6 mm
Width 60 mm
net weight 0.8 kg
Output coupling Parallel,Serial
Mounting support Top hat type TH35-15 rail conforming to IEC 60715,Top hat type TH35-7.5 rail conforming to IEC 60715,Double-profile DIN rail
Supply SELV conforming to IEC 60950-1,SELV conforming to IEC 60204-1,SELV conforming to IEC 60364-4-41
Dielectric strength 3000 V AC with input to output
Service life 10 year(s)
Overvoltage category II

Environment

Standards IEC 62368-1,EN/IEC 61204-3,IEC 61000-6-1,IEC 61000-6-2,IEC 61000-6-3,IEC 61000-6-4,IEC 61000-3-2,EN 61000-3-3,UL 62368-1,CSA C22.2 No 62368-1,UL 508,CSA C22.2 No 107.1,EN/IEC 62368-1
Product certifications CE,CUL listed,CUL recognized,RCM,CB Scheme,EAC,KC
Operating altitude < 5000 m
Shock resistance 150 m/s² for 11 ms
IP degree of protection IP20
Ambient air temperature for operation -20…40 °C without derating mounting position A 115 V AC < 2000 m,-20…50 °C without derating mounting position A 230 V AC < 2000 m,40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC < 2000 m,50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m
Electrical shock protection class Class I
Pollution degree 2
Vibration resistance 3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6,10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
Electromagnetic immunity Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2,Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2,Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3,Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3,Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3,Immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4,Surge immunity test - test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5,Surge immunity test - test level: 3 kV (between phases) conforming to IEC 61000-4-5,Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to IEC 61000-4-6,Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8,Immunity to voltage dips conforming to IEC 61000-4-11,Disturbing field emission conforming to EN 55016-2-3,Limits for harmonic current emissions conforming to IEC 61000-3-2, conforming to EN 55016-1-2, conforming to EN 55016-2-1
Electromagnetic emission Conducted emissions conforming to IEC 61000-6-3,Radiated emissions conforming to IEC 61000-6-4

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.000 cm
Package 1 Width 17.500 cm
Package 1 Length 18.000 cm
Package 1 Weight 974.000 g
Unit Type of Package 2 S03
Number of Units in Package 2 9
Package 2 Height 30.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 9.147 kg
Unit Type of Package 3 P12
Number of Units in Package 3 72
Package 3 Height 45.000 cm
Package 3 Width 80.000 cm
Package 3 Length 120.000 cm
Package 3 Weight 85.200 kg

Contractual warranty

Warranty 18 months

Documentation

Product Datasheet

Instruction sheet

Catalogue

CAD

Environmental disclosure

Looking for a specific part?

If the product you're searching for isn't listed, click below to submit your enquiry and one of our specialists will source it for you.

CTA image

Contact Us

Using one of the ways below contact us and we will get back to you as soon as possible